SOCIAL
INFRASTRUCTURE

Social Infrastructure

Top / Products & Solutions / Social Infrastructure / Class II SPD

Class II SPD

SPD designed to protect against induced lightning

Class II SPD

Features

  • JIS C 5381-11:2014 Class II compliant
  • Signal output is standard equipment
  • Plugin Type
  • Compliant with standard specifications for public building construction
  • Conforms to building equipment design standards

Model

  • HMG-C-R-300(3+1)

Applicable power distribution method

  • Single-phase two-wire system / Single-phase three-wire system / Three-phase three-wire system / Three-phase four-wire system

SPECIFICATIONS(L-N / N-PE)

Maximum continuous operating voltage Uc (AC)

300V / 305V

Nominal discharge current In (8/20μs)

20kA / 40kA

Maximum discharge current Imax (8/20μs)

50kA / 65kA

Impulse current Iimp (10/350μs)

Voltage protection level up

< 1500V

remarks
  • A separate external separator is required.
  • Please refer to the catalog for other lineups.

*If the table cannot be displayed in its entirety, please scroll horizontally to view it.